Light-O-Rama Protocol

This documentation covers the Light-O-Rama (LOR) communication protocol for AC lighting control units. It has been manually reverse engineered using the LOR Hardware Utility, serial port monitoring software and LOR1602Wg3 & CTB16PCg3 units. Given the reverse engineered nature, this documentation should be considered incomplete, incorrect and outdated.

Test Environment

From my testing, the protocol seems consistent across firmware versions and is unlikely to change. You can view your current firmware version in the LOR Hardware Utility. I have provided my firmware and unit models for reference.

Unit Model Firmware Version Channel Count
1x LOR1602Wg3 1.12 16
1x CTB16PCg3 1.09 16
3x CTB16PCg3 1.11 16

Each of my units have 16 channels. I have kept alternate channel count configurations in mind while documenting the protocol and as such you should have no issues applying it to other network configurations.

I am using a 57.6K baud rate and the Light-O-Rama provided USB-RS485 adapter.

Network

Fault Tolerance

Messages are generally "fire and forget". Your software implementation SHOULD avoid resending previous messages since it may interrupt ongoing effect executions (like restarting a timer), resulting in channel output glitches.

Some software implementations may choose to ocassionally repeatedly resend messages as a "sanity" measure. However this mostly wastes network bandwidth and risks the aforementioned glitches. If you choose to repeatedly resend messages, avoid sending messages which execute over a period of time.

Heartbeat Behavior

Every 500ms the LOR Hardware Utility broadcasts a heartbeat message onto the network. This message is not unit specific and should only be sent once per "heartbeat".

If a unit has not received a heartbeat message within 2 seconds, it will mark itself not connected and become inactive. This is indicated by the hardware with a message on its LCD (if any), or a blinking LED.

To "re-activate" the units, simply restart sending the heartbeat message.

Notes

  • Units do not mind changes in heartbeat message frequency as long as it is within the timeout interval.
  • Some units may require several heartbeats to pass before re-activating. Software implementations MAY wish to wait 1-5 seconds when starting to ensure all units have been activated.

Empty Bytes

An empty byte (0x00) appears to be used to execute each unit's incoming network buffer. You must send these empty bytes, otherwise units will never execute the messages you've sent.

It is RECOMMENDED you prefix messages with an empty byte to ensure the buffer is flushed prior to the incoming message, improving fault tolerance by preventing corrupt/invalid messages from remaining in the buffer. Appending an additional empty byte to the end of the message means it will be executed as soon as the empty byte is received.

Notes

  • 0x00 does not otherwise appear in the protocol, even as a value.
  • To reduce bandwidth usage, you may be able to omit the empty byte in some places. The LOR Sequencer appears to automatically do this when sending multiple messages. If you find your unit is not executing messages properly, consider introducing additional empty bytes.
  • In my monitoring I have seen empty bytes consistently sent over the network. This may be either to either flush an outbound queue, or to simply ensure that even with data loss, the message buffer is still being flushed.

Data Types & Encoding Formats

Unit IDs

The LOR protocol supports up to 240 unique unit IDs. Given that 0x00 is effectively unavailable namespace, the valid unit ID range is 0x01 to 0xF0 (240). Any unit ID above 0xF0 is reserved, often used for routing information.

Since messages are not consumed by units, multiple units may have the same unit ID. They would simply act as clones of each other when receiving messages. This is however discouraged since software implementations may not properly handle multiple responses to messages direct at a single unit ID.

Value Purpose
0xFF "Any unit ID", used for broadcasting messages
0xFE Represents the controlling program, used for replying to messages
0xFB Used by the LOR Hardware Utility when uploading MP3 & sequence files
0xFA Used within an unknown message sent by the LOR Hardware Utility when the program is first launched
0xF1 Used by the LOR Hardware Utility when setting "Any" unit's ID

Tip: Wherever a unit ID is specified, you may choose to subsitute it for the 0xFF broadcast flag. This makes it easy to avoid manually sending the same message to multiple units.

Channel IDs

While channel IDs start at 1 within LOR software and user guides, they start at 0 within the protocol. This documentation will also consider channel IDs as starting at 0. The following code sample shows how to calculate a protocol equivalent of a channel ID by ORing it, as well as reversing this by taking its AND of NOT 0x80. Channel numbers greater than or equal to 127 (the max value that can fit a uint8 with the 0x80 offset) should be encoded as multiple bytes in big endian format. Each byte should still be offset by 0x80.

uint8_t to_protocol_channel(uint8_t channel) {
	return channel | 0x80;
}

uint8_t from_protocol_channel(uint8_t protocol_channel) {
	return protocol_channel & ~0x80;
}

Brightness

Brightness is encoded as a uint8 between 0x01 (100% brightness) and 0xF0 (0% brightness). Values outside these min/max bounds seem to result in indeterminate and unreliable behavior.

You can convert a normalized value [0, 1] into a brightness value like so:

brightness_value = normalized_value * (0x01 - 0xF0) + 0xF0

Notes

  • The provided code sample results in a linear brightness curve. Some program implementations, such as xLights, may use a custom curve function. The brightness curve's behavior is up to the developer and is not restricted by the hardware beyond the previously specified min/max values.
  • These values have been captured as output of the LOR Hardware Utility.
  • The datasheet for my LOR1602Wg3 unit specifies "100 intensity levels for dimming". So while additional brightness precision is supported within the protocol, your hardware may disregard it.

Durations

As displayed within the LOR Hardware Utility (and cross validated in the datasheet for my LOR1602Wg3 unit), durations have a minimum value of 0.1s and a maximum of 25s with 256 available levels between those values.

Durations are encoded as a uint16 as a scaled value against the max and min limits. For durations that fit within the lower byte, the upper byte MUST be set to 0x80 so that it is ignored by the unit.

The following code sample accomplishes this by ORing the uint16 value against 0x80 shifted left by 8 bits. The magic value 5099 is derived from the encoded representation of the minimum duration, 0.1s.

// This example assumes seconds value is already within the acceptable range
uint16_t lor_duration(float seconds) {
    const uint16_t scaled_value = (uint16_t) roundf(5099 / (seconds / 0.1F));
    if (scaled_value > 0xFF) {
        return scaled_value;
    } else {
        return 0x8000 | scaled_value;
    }
}

Examples

Duration Scaled Value Encoded Value
0.1s 5099 0x13EB
0.5s 1020 0x03FC
1s 510 0x01FE
2s 255 0x80FF
25s 20 0x8014

Notes

  • Any duration greater than 2 seconds fits within a single byte.
  • The scale used is exponentialish and offers higher precision for lower value durations. For example, the delta of the scaled values of 0.1s and 0.2s is 232x larger than the delta between the scaled values of 2.1s and 2.2s.
  • Any scale could technically be applied atop this behavior assuming the resulting encoded values stay within the value range. Your unit however may disregard or round this value - consult your unit's datasheet.

Actions

Actions are predefined lighting effects, typically built into the hardware. These are what make up the majority of the network traffic since they are the effective purpose of the software and hardware. An action defines what a target should do, but does NOT specify the target directly. Instead, actions are wrapped into messages, which specify the target, the action, and any metadata required by the action.

Name Value Description Has Metadata
Set Light State(s) 0x01 Sets a single channel to 100% brightness, or the absolute brightness (0% or 100%) of multiple channels according to a channel mask No
0x02
Set Brightness 0x03 Sets a channel's brightness Yes
Fade 0x04 Fades a channel between two brightness values according to a duration Yes
Fade Loop 0x05 Infinitely fades a channel between zero/full brightness according to a duration Yes
Set Twinkle 0x06 Sets a channel to twinkling mode No
Set Shimmer 0x07 Sets a channel to shimmer mode No

See Light-O-Rama's Effects documentation for more information and examples.

Metadata Structures

Set Brightness

Name Data Type
Brightness uint8

Fade

Name Data Type
Start Brightness uint8
End Brightness uint8
Duration uint16

Fade Loop

This action appears to loop infinitely, assuming the connection remains active. The duration corresponds to one half of the fade effect. There is (seemingly) no way to end the fade effect without the possibility of interrupting it. I cannot find any usages of this effect within Light-O-Rama's official software.

Name Data Type
Duration uint16

Messages

Heartbeat

Field Data Type Value Notes
Unit ID uint8 0xFF Denotes a broadcast message
Configuration Update uint8 0x81 Commonly seen used in messages relating to configuration data
Heartbeat uint8 0x56

Get Unit Version

Fetching the firmware version requires a message to be sent and a response received. The response message does not contain a unit ID. As a result, for software implementations looking to scan the network, you must wait a period of time after each sent message for a response, before moving on to the next unit ID.

Request

Field Data Type Value Notes
Unit ID uint8 0xFF
Firmware Request Type uint8 0x88 Seem in firmware upload messages
Data Request Type uint8 0x29 Variations of this message have been seen with values 0x2A and 0x2B when changing/setting unit IDs
uint8 0x2D

Response

Field Data Type Value Notes
Response uint8 0xFE 0xFE is used for routing messages back to the controlling software
Data Response Type uint8 0x29 Matches value in request message
Unit Type uint8 Unit hardware model, correponds to the "Type" column of the LOR_DeviceFile.txt
uint8 0x81
uint8 0xFF
Firmware Version 1 uint8 ASCII value of the firmware's 1st minor version number
Firmware Version 2 uint8 ASCII value of the firmware's 2nd minor version number
uint8 0x80
uint8 0x03 Potentially unit ID
uint8 0x03 Potentially unit ID
uint8 0xF0

For example firmware version "1.09" has minor version numbers of 0 and 9. These are sent as their ASCII values (0x30 & 0x39). Only the minor version numbers seem to be included in the response message. This is supplemented by the fact that the LOR_DeviceFile.txt hardcodes the major version into the "Description" column.

Notes

  • This is used by the LOR Hardware Utility when determining if a unit ID is in use for ID changes, or when hitting the "Refresh" button and scanning the network.
  • The LOR Hardware Utility will send this 5 times, with a delay between each request, for each unit ID it is checking until it gets a response. If it has not received a response after all 5 requests, it considers the unit ID unused or absent.

All Off

Turns off all channels attached to the unit ID without any filtering capability.

Tip: Unit ID 0xFF will broadcast this to all units. This allows you to easily turn off EVERYTHING with a single message.

Field Data Type Value
Unit ID uint8
Action uint8 0x41

Background Fade

Background Fade enables applying a foreground action atop a background action. This allows execution of multiple single channel actions simultaneously on the same channel. The structure is equivalent to the two actions joined with a 0x81 magic number.

While other action values may be used, only Set Shimmer and Fade seem to produce results without clashing.

Field Data Type Value Notes
Unit ID uint8
Foreground Action uint8
Channel uint8 Supports single channel ID and channel masks
Magic Number uint8 0x81 Denotes extended message?
Background Action uint8
Start Brightness uint8
End Brightness uint8
Duration uint16

Single Channel Action

Executes an action (and its metadata, if any) on the single specified channel. If broadcasted, this will apply to the specified channel ID of each unit (assuming it has enough channels).

Name Data Type
Unit ID uint8
Action uint8
Action Metadata
Channel ID uint8

Multi Channel Action

Multi channel actions utilize the same actions and metadata structures as their single channel equivalents with the exception that instead of sending a uint8 channel ID a channel bitmask is sent and the channel mask length is included as part of the action value. For units with more than 16 channels, multiple messages are sent instead, each providing a portion of the full channel mask.

Field Data Type Notes
Unit ID uint8
Action uint8 Action value OR'd against a magic number
Action Metadata
Chain Index uint8/- Only sent when chaining multi channel messages due to the full channel configuration being unable to fit within a single channel mask
Channel Mask uint8[] Length is dependent on channel count, channels with a 0 value bit are ignored and maintain their previous state

Channel Masking

The channel mask for channels 1, 7 and 14 in binary is 0010 0000 0100 0001.

uint16_t mask = 0;
mask |= 1 << 0 // set bit index 0 (channel 1) to 1
mask |= 1 << 6 // set bit index 6 (channel 7) to 1
mask |= 1 << 13 // set bit index 13 (channel 14) to 1

The resulting channel mask is 16 bits long and is encoded as 0x2041.

To determine the magic number used, round the length of your channel mask up to the nearest multiple of 8, select the magic number from the table below, and OR it against your action value.

Channel Mask Length Mask Notes
8 bits 0x30
16 bits 0x10 Tip: 0x10 has a decimal value of 16
16 bits 0x50 Only used when chaining messages
uint8_t get_multi_channel_action(uint8_t action, uint8_t channel_mask_length) {
	if (channel_mask_length == 8) {
		return 0x30 | action;
	} else if (channel_mask_length == 16) {
		return 0x10 | action;
	} else {
		// For channel mask lengths greater than 16, multiple messages are sent instead.
		// A magic number of 0x50 is used, regardless of channel mask length
		return 0x50 | action;
	}
}

In the previous example, 16 is already a multiple of 8, so a 0x10 magic number is selected. A "Fade" action (0x04) would be OR'd against the selected magic number (0x10), resulting in a final action value of 0x14.

Chaining Example

Given a unit ID of 0x01 with 64 channels, we can set every channel to 0% brightness using 4 multi channel messages. The chain index is a reverse index, starting at the highest index plus 0x01, ending at 0x01. It must not be 0x00, which marks the end of a message.

# Set Brightness of channels 0-15 (padding bytes omitted)
0x01 (unit ID)
0x53 (Chaining channel mask magic number | 0x03 Set Brightness action)
0xF0 (0% brightness)
0x03 (chain index of 3)
0xFF (channel mask pt. 1)
0xFF (channel mask pt. 2)

Resending this message with a chain index of 2 and 1 would provide channel masks for channels 16-31 and 32-47 respectively. To end the chain, a final message is sent with an unchained action value offset and without a chain index.

# Set Brightness of channels 48-63 (padding bytes omitted)
0x01 (unit ID)
0x13 (16-bit channel mask magic number | 0x03 Set Brightness action)
0xF0 (0% brightness)
0xFF (channel mask pt. 1)
0xFF (channel mask pt. 2)

Notes

  • Channel mask lengths can be mixed. For example, 40 channels could be sent as 2x 16 bit masks and 1x 8 bit mask.
  • Units safely handle channel masks larger in length than the channel count, however they should be avoided to optimize bandwidth and processing speed.

Undocumented

These messages have been captured, and are noted here to help cross reference recurring magic numbers.

# LOR Hardware Utility Boot
Sent 5 times by the LOR Hardware Utility when booting.
0xFA 0x88 0x31 0x2D

# Edit Mode
Appears whenever modifying a unit's configuration or updating firmware.
$UNIT_ID 0x8A 0x56

# Firmware upload
Various captured stages of the firmware update process

fe cb da 01 ff ff ff ff ff 01 <- Initial channel configuration
fe cb da 02 ff 0b ff ff ff 01 <- Firmware blob (n...)
fe cb da 03 ff 08 ff ff ff 01 <- Last firmware blob

0x01, 0x02, 0x03 denote upload stage

0x01 = Start
0x02 = Data part
0x03 = Finish

Each firmware blob part is sent with the message header 0xFF 0x89 0x02.
Units respond to each blob part with:

fe cb da 02 ff 0b ff ff ff 01

0xDA = 218, Bootloader version?

Notes

  • #FILE marker within firmware files is the last 4 bytes of Fletcher-64 checksum of the re-assembled firmware file.
  • Firmware files get split at carriage returns (0x0D 0x0A). Heartbeats are sent in their place. Each carriage return denotes a "blob", with the last blob placed first in the file.
  • Firmware values have some sort of bitpacking encoding. They do not contain values [0,32][35][251-255].