!DEFINE TRANSFORMERS FOR REGULATORS
! Have to assume basically zero impedance regulators to match the test case
new transformer.reg2a phases=1 windings=2 bank=reg2 buses=[9.1 9r.1] conns=[wye wye] kvs=[2.402 2.402] kvas=[2000 2000] XHL=.01 %LoadLoss=0.00001 ppm=0.0
new transformer.reg3a phases=1 windings=2 bank=reg3 buses=[25.1 25r.1] conns=[wye wye] kvs=[2.402 2.402] kvas=[2000 2000] XHL=.01 %LoadLoss=0.00001 ppm=0.0
new transformer.reg4a phases=1 windings=2 bank=reg4 buses=[160.1 160r.1] conns=[wye wye] kvs=[2.402 2.402] kvas=[2000 2000] XHL=.01 %LoadLoss=0.00001 ppm=0.0
new transformer.reg3c like=reg3a bank=reg3 buses=[25.3 25r.3] ppm=0.0
new transformer.reg4b like=reg4a bank=reg4 buses=[160.2 160r.2] ppm=0.0
new transformer.reg4c like=reg4a bank=reg4 buses=[160.3 160r.3] ppm=0.0
! POINT REGULATOR CONTROLS TO REGULATOR TRANSFORMER AND SET PARAMETERS
new regcontrol.creg2a transformer=reg2a winding=2 vreg=120 band=2 ptratio=20 ctprim=50 R=0.4 X=0.4
new regcontrol.creg3a transformer=reg3a winding=2 vreg=120 band=1 ptratio=20 ctprim=50 R=0.4 X=0.4
new regcontrol.creg3c like=creg3a transformer=reg3c
new regcontrol.creg4a transformer=reg4a winding=2 vreg=124 band=2 ptratio=20 ctprim=300 R=0.6 X=1.3
new regcontrol.creg4b like=creg4a transformer=reg4b R=1.4 X=2.6
new regcontrol.creg4c like=creg4a transformer=reg4c R=0.2 X=1.4
! NOTE: WHEN LIKE= IS USED, IT IS NECESSARY TO SPECIFY ONLY THOSE PROPERTIES THAT ARE DIFFERENT