! simple reverse mode regulator test
! puts enough DG on the IEEE 123 test case to force reverse flow
! regulators see reverse power go to neutral
Compile (IEEE123Master.dss)
RegControl.creg1a.maxtapchange=1 Delay=15 !Allow only one tap change per solution. This one moves first
RegControl.creg2a.maxtapchange=1 Delay=30 !Allow only one tap change per solution
RegControl.creg3a.maxtapchange=1 Delay=30 !Allow only one tap change per solution
RegControl.creg4a.maxtapchange=1 Delay=30 !Allow only one tap change per solution
RegControl.creg3c.maxtapchange=1 Delay=30 !Allow only one tap change per solution
RegControl.creg4b.maxtapchange=1 Delay=30 !Allow only one tap change per solution
RegControl.creg4c.maxtapchange=1 Delay=30 !Allow only one tap change per solution
Set MaxControlIter=30
! Solve executes the solution for the present solution mode, which is "snapshot".
New energymeter.M1 Line.sw1 1
solve
New Monitor.4a Transformer.reg4a 2 mode=2
New Monitor.4b Transformer.reg4b 2 mode=2
New Monitor.4c Transformer.reg4c 2 mode=2
New Monitor.P4a Transformer.reg4a 2 mode=1 ppolar=no
New Monitor.P4b Transformer.reg4b 2 mode=1 ppolar=no
New Monitor.P4c Transformer.reg4c 2 mode=1 ppolar=no
Redirect SetDailyLoadshape.DSS
solve
solve Mode=daily
! define the generator
New Generator.2MWGen Bus1=450 kV=4.16 kW=1400 PF=1
solve
regcontrol.creg4a.reversible=yes revneutral=yes
regcontrol.creg4b.reversible=yes revneutral=yes
regcontrol.creg4c.reversible=yes revneutral=yes
solve
Show monitor 4a
Show taps
Show Powers kva Elements
Export monitors 4a
Plot monitor object= 4a channels=(1 )
Export monitors p4a
Plot monitor object= p4a channels=(1 )