Compile (IEEE123Master.dss)
RegControl.creg1a.maxtapchange=1 Delay=15 !Allow only one tap change per solution. This one moves first
RegControl.creg2a.maxtapchange=1 Delay=30 !Allow only one tap change per solution
RegControl.creg3a.maxtapchange=1 Delay=30 !Allow only one tap change per solution
RegControl.creg4a.maxtapchange=1 Delay=30 !Allow only one tap change per solution
RegControl.creg3c.maxtapchange=1 Delay=30 !Allow only one tap change per solution
RegControl.creg4b.maxtapchange=1 Delay=30 !Allow only one tap change per solution
RegControl.creg4c.maxtapchange=1 Delay=30 !Allow only one tap change per solution
Set MaxControlIter=30
! Solve executes the solution for the present solution mode, which is "snapshot".
New energymeter.M1 Line.sw1 1
solve
! 1000-sec Wind output at 1 s interval
New Loadshape.WindRamp npts=1000 Interval=(1 3600 /) mult=(file=Windoutput.txt)
New Monitor.4a Transformer.reg4a 2 mode=2
New Monitor.4b Transformer.reg4b 2 mode=2
New Monitor.4c Transformer.reg4c 2 mode=2
New Monitor.P4a Transformer.reg4a 2 mode=1 ppolar=no
New Monitor.P4b Transformer.reg4b 2 mode=1 ppolar=no
New Monitor.P4c Transformer.reg4c 2 mode=1 ppolar=no
solve
! define the generator
New Generator.2MWGen Bus1=450 kV=4.16 kW=2300 PF=1 Duty=WindRamp
! Solve and let regulators settle out with generator on line
Solve
regcontrol.creg4a.reversible=yes revneutral=yes ! debug=yes
regcontrol.creg4b.reversible=yes revneutral=yes
regcontrol.creg4c.reversible=yes revneutral=yes
! Run 1000-point dutycycle
Solve mode=dutycycle number=1000 stepsize=1s
Plot monitor object= 4a channels=(1 )
Plot monitor object= p4a channels=(1 )
Plot monitor object= 4b channels=(1 )
Plot monitor object= 4c channels=(1 )
Plot monitor object= p4b channels=(1 )
Plot monitor object= p4c channels=(1 )
solve
Plot monitor object= 4a channels=(1 )
Plot monitor object= p4a channels=(1 )