# Service_Water_Heating - Rule 11-7
**Schema Version:** 0.0.36
**Schema Version:** 0.0.37

**Mandatory Rule:** TRUE

**Rule ID:** 11-7

**Rule Description:** Except in buildings that will have no service water heating loads, the service water heating systems type in the baseline building design shall be as specified in Table G3.1.1-2 for each building area type in the proposed design.
**Rule Description:** Except in buildings that will have no service water heating loads, the service water heating system type in the baseline building design shall be as specified in Table G3.1.1-2 for each building area type in the proposed design.

**Rule Assertion:** Options are PASS/FAIL

**Appendix G Section Reference:** Table G3.1 #11, baseline column, a & b

**Evaluation Context:** B-RMD each SWH Equipment
**Evaluation Context:** B-RMD each SWH Equipment
**Data Lookup:**
- **Table G3.1.1-2(shw_bat)**
**Function Call:**
- **get_component_by_id**
- **get_SHW_equipment_associated_with_each_SWH_bat**
- **get_SHW_types_and_SHW_use**
- **get_SHW_equipment_type**
- **Table G3.1.1-2(swh_bat)**
**Function Call:**
- **get_component_by_id**
- **get_SWH_equipment_associated_with_each_SWH_bat**
- **get_SWH_bats_and_SWH_use**
- **get_SWH_equipment_type**

**Applicability Checks:**
- Each SHW use type is applicable if there are SHW loads
- use get_SHW_equipment_associated_with_each_SWH_bat to get the SHW use types and SHW use in the building: `shw_bats_and_equip_dict = get_SHW_equipment_associated_with_each_SWH_bat(B_RMD)`
- Note: Applicability is determined at the building segment level, but the rule is evaluated for all SWH equipment serving the building segment.
- Each SWH bat is applicable if there are SWH loads in the BAT in the proposed model

- call the function get_SHW_types_and_SHW_use for the proposed: `shw_bat_and_use_dict_p = get_SHW_types_and_SHW_use(P_RMD)`
- look through each of the SHW bats in the building: `for shw_bat in shw_bat_and_use_dict_p:`
- check if there are SHW loads in this use type, continue to rule logic: `if len(shw_bat_and_use_dict_p[shw_bat]) > 0: CONTINUE TO RULE LOGIC`
- otherwise, rule is not applicable for this shw_bat: `else: NOT_APPLICABLE`
- call the function get_SWH_bats_and_SWH_use for the proposed: `swh_bats_and_uses_p = get_SWH_bats_and_SWH_use(P_RMD)`
- look through each of the SWH bats in the building: `for swh_bat in swh_bats_and_uses_p:`
- look at each service water heating use in the BAT: `for swh_use_id in swh_bats_and_uses_p[swh_bat]:`
- get the swh use from the swh_use_id: `swh_use = get_component_by_id(P_RMD, swh_use_id)`
- check if there are SWH loads in this use, continue to rule logic. In this case, we are not worried about the use_units, we just want to know that there is a use that is greater than 0: `if swh_use.use > 0: CONTINUE TO RULE LOGIC`
- otherwise, rule is not applicable for this swh_bat: `else: NOT_APPLICABLE`

## Rule Logic:
- look at each SWH Equipment in the shw_bat - there should only be one, but this is checked in rule 11-8: `for swh_equip_id in shw_bats_and_equip_dict[shw_bat]["SHWHeatingEq"]:`
- get the SHW equipment type using the function get_SHW_equipment_type: `shw_equip_type = get_SHW_equipment_type(B_RMD, swh_equip_id)`
- get the expected SHW equipment type by looking it up in the table G3.1.1-2: `expected_shw_equip_type = data_lookup(Table G3.1.1-2, shw_bat)`
- use get_SWH_equipment_associated_with_each_SWH_bat to get the SWH use types and SWH use in the building: `swh_bats_and_uses_b = get_SWH_equipment_associated_with_each_SWH_bat(B_RMD)`
- look at each SWH Equipment in the swh_bat. Appendix G requires only one system per bat, but this is covered in rule 11-8, so here we will allow multiple SWH equipment: `for swh_equip_id in swh_bats_and_uses_b[swh_bat]["SWHHeatingEq"]:`
- get the SWH equipment type using the function get_SWH_equipment_type: `swh_equip_type = get_SWH_equipment_type(B_RMD, swh_equip_id)`
- get the expected SWH equipment type by looking it up in the table G3.1.1-2: `expected_swh_equip_type = data_lookup(Table G3.1.1-2, swh_bat)`



## Rule Assertion:
- Case1: the expected_shw_equip_type matches shw_equip_type: PASS: `if expected_shw_equip_type == shw_equip_type: PASS`
- Case2: the expected_shw_equip_type doesn't match shw_equip_type, `FAIL: else: FAIL`
- Case1: the expected_swh_equip_type matches swh_equip_type: PASS: `if expected_swh_equip_type == swh_equip_type: PASS`
- Case2: the expected_swh_equip_type doesn't match swh_equip_type, `FAIL: else: FAIL`


**Notes:**
1. The rule states bats for the proposed, but this is complex to check - can we add that SHW uses need to have the same use type to the section 1 general checks?
1. The rule states bats for the proposed, but this is complex to check - can we add that SWH uses need to have the same use type to the section 1 general checks?